Completely New System

A Completely New System is defined as changing all components including New Duct Work.

In Climate Zones 2, & 8-15  the HERS testing requirements are a Refrigerant Charge and Airflow Test (RCA) with a Duct Sealing test (must test < 6% of rated fan flow) and if the address is in Climate Zone 10-15 (2, 8 & 9 exempt) an added Cooling Coil Airflow Test (CCA) (minimum of 350 CFM / Ton) and a Fan Watt Draw (FWD) (max 0.58 Watts / based on CCA Test) are required.

If all components were changed but not ducts,

In Climate Zones 2, & 8-15  the HERS testing requirements are a Refrigerant Charge and Airflow Test (RCA) with a Duct Sealing test (must test < 15% of rated fan flow) and if the address is in Climate Zone 10-15 (2, 8 & 9 exempt) an added Cooling Coil Airflow Test (CCA) (minimum of 300 CFM / Ton) is required.

Click this link to   Find Your Climate Zone                                                                                                               Return to Compliance Certificates
If it is a Completely New System, we can get that project registered and the testing done to complete the project. Contact us at 760-646-2589 or 760-530-0712. Let's get the project finished and the paperwork done.